For example the full load current of a 5 hp motor at 460v is 7 6 amps.
Motor circuit breaker sizing.
This article will address the history use and recent developments in available high resistance grounding technology used with ungrounded voltage systems.
Size the branch circuit short circuit and ground fault protection device per 240 6 a and 430 52 c 1 ex.
Unrestrained fault current can cause severe equipment damage product destruction and personnel injury.
Breaker cannot be larger than ampacity of wire except for motors and a few other loads.
As circuit breakers cbs and overcurrent protection devices ocpd are designed for 100 rated current i e.
High resistance grounding is a means of limiting ground fault current in electrical systems.
1 1 2 3 5 7 10 15 20 25 30 40 50 60 75 100 125 150.
Breaker size must be rated for a minimum of 125 of the full load current of the motor it is protecting rounded up to the next standard breaker size.
Let s try sizing a motor feeder conductor.
For an inverse time breaker.
Locate where your motor falls in table 430 52 based on the full load current and motor size.
This table is used to size the short circuit protection check the motor data sheets for the motor s full load current.
Circuit breaker size 2.
Table 2 load maximum circuit breaker size of current.
Maximum loading of any circuit breaker is 80 of rating for non motor loads with exceptions as noted below.
The table will give you the size of the short circuit protection as a percentage of the full load current.
The fuse sizing in column 4 for lps rk sp lpn rk sp frs r and frn r fuses provides a degree of motor and circuit overload protection to back up the normal motor overload protective device.
80 of breaker max single phase breaker size wire size based on copper thhn wire increase one size when using aluminum conductors at 115 volts at 230 volts 15 amp 14 1 380 2 760 20 amp 12 1 840 3 680 30 amp 10 seldom used on 115 voltage 5 520 40 amp 8 seldom used on 115 voltage 7 360 50 amp 6 seldom used on 115 voltage 9 200 60.
Difference between circuit breaker and isolator disconnector circuit breaker size calculation for continuous non contentious load.
22a x 2 5 55a next size up 60a.
Minimum circuit size is 12 with 20 amp cb.
The breaker must be sized for 7 6 1 25 10 amps.
A 30a circuit breaker can safely carry the exact 30a current but nec suggests 80 as a safe current limit as compared to the rated current.
This level of protection requires a well designed true dual element fuse.